(Model # PT2X2FIT) Note: Picture may not represent the actual product. We are continuously working on improving our website and reserve the right to change specifications, availability, and pricing without prior notice. Two-Piece 2 x 2 Through-Floor Fitting is Fire-Rated Poke-Through ScrubShield 2 X 2 Flush.
Through-floor Fitting Features:
- Fitting does not include Cover and Flange
- Includes Hubbell HBL2162BK duplex receptacle: Black, NEMA 5-20R; 20 A, 125 V AC
- Complies with UL 514A requirements for scrub water protection
- Fire Rating: For use in 1, 1 1/2, 2, 3, or 4 hour rated unprotected reinforced concrete floors or in 1, 2, or 3 hour rated floors employing steel floor units and concrete topping (D900 series design)
- Floor Thickness Range: 2 1/4" (over metal deck) to 7"
- UL Installation Spacing: Minimum of 2' on centers and not more than one unit per 65 sq. ft. of floor area in each span
- Cored Hole: 3" Diameter
- Device and Cover Flap Material: Thermoplastic
- Carpet Flange Material: Painted Cast Aluminum/Solid Brass, Brushed and Laquered
- Plenum Rating: Acceptable for use in environment air handling spaces per NEC article 300.22(C)
- Conduit Tubes: Power - 3/4" EMT/Low Voltage - 1/2" EMT (two)
| |
|